Executive Summary
This lesson introduces fundamental concepts of electrical current and voltage, clearly defining new terminology as you progress through the material.
Key topics covered in this lesson include:
- AC vs. DC Power: The differences between alternating and direct current, including the practical advantages of AC power transmission over long distances.
- Electromagnetism: The relationship between electric current and magnetism, featuring the “left-hand rule” for determining magnetic field direction around a conductor.
- AC Generation: Methods for producing alternating current and the mathematical relationships among frequency, period, time, and wavelength.
- Waveform Calculations: How to compute peak-to-peak, instantaneous, effective, and average values of voltage and current, as well as the phase difference between sine waves.
ALTERNATING CURRENT
Alternating current (AC) is a current that constantly changes in amplitude and reverses direction at regular intervals. Direct current (DC) flows only in one direction, and the amplitude of the current is determined by the number of electrons flowing past a point in a circuit in one second. If, for example, a coulomb of electrons passes a point in a wire in one second and all the electrons are moving in the same direction, the direct current in the wire is one ampere.
Similarly, if 0.5 coulomb of charge moves past a point in a wire in one direction during half a second, and then 0.5 coulomb moves past the same point in the opposite direction during the next half-second, then 1 coulomb of charge has moved past that point in total during one second. However, the net charge transfer over the full second is zero because the direction is reversed. If the current is constant at 1 ampere during each half-second, first in one direction and then the other, the alternating current has a magnitude, or peak value, of 1 ampere.
DISADVANTAGES OF DC COMPARED TO AC
When commercial use of electricity became widespread in the United States, early direct-current (DC) systems had an important limitation: changing DC voltage efficiently was difficult with the equipment available at the time.
For example, operating a 120-volt lamp from a 240-volt DC source required a way to reduce the voltage across the lamp. One method was to connect a properly sized resistor in series with the lamp. The resistor would drop the extra 120 volts, but it would also waste energy as heat. Because the resistor and lamp carried the same current and each had a 120-volt drop, the resistor would consume as much power as the lamp.
Transmitting electricity over long distances presented another challenge. Transmission wires have resistance, which converts some electrical energy into heat.
This power loss is calculated using:
Power loss = I2R.
Where:
- I = current through the wire in amperes.
- R = resistance of the wire in ohms.
For the same amount of power transmitted, increasing the transmission voltage allows the current to decrease. Lower current reduces the power lost as heat in the wires. This principle applies to both AC and DC transmission.
AC had a major practical advantage over early DC systems because transformers could efficiently increase or decrease AC voltage. A conventional transformer operates using changing magnetic flux and cannot continuously transform steady DC voltage directly.
At a generating station, a step-up transformer increases the AC voltage for transmission. For approximately the same power, this higher voltage means lower current and lower transmission losses. Near consumers, step-down transformers reduce the voltage to levels suitable for distribution and use by electrical equipment.
The ability to change voltage efficiently helped AC become the standard for most utility distribution systems.
Modern technology has overcome many limitations of early DC systems. Electronic converters can change DC voltage levels, and high-voltage direct-current (HVDC) systems are used to transmit large amounts of electrical power over long distances. Converter stations connect these DC transmission systems to AC power networks, so consumers do not have to operate equipment at the high transmission voltage.
AC remains widely used for utility distribution, while DC serves important roles in batteries, solar photovoltaic systems, electronic equipment, and HVDC transmission.
VOLTAGE WAVEFORMS
You now know that there are two types of current and voltage: direct and alternating.
If a graph is constructed showing the amplitude of a DC voltage across the terminals of a battery as a function of time, it will appear in view A of the figure below. The DC voltage has a constant amplitude.
Some voltages undergo periodic amplitude changes, as shown in view B. The pattern that results when these amplitude changes over time are plotted on graph paper is known as a waveform.
View B shows some of the common electrical waveforms. Of those illustrated, the sine wave will be dealt with most often.

ELECTROMAGNETISM
The sine wave illustrated below shows a current whose amplitude and direction change.

Basic Electrical Theory discussed the fundamental theories of simple magnets and magnetism, but only briefly mentioned how magnetism can be used to produce electricity.
This lesson will give you a more in-depth study of magnetism.
The main points to be explained are how magnetism affects an electric current and, conversely, how an electric current affects magnetism.
This general subject area is most often called electromagnetism. To properly understand electricity, you must first become familiar with the relationships between magnetism and electricity.
For example, you must know that:
- An electric current always produces some form of magnetism.
- The most common way to produce or use electricity involves magnetism.
- Magnetic influences cause electricity to behave peculiarly under certain conditions.
When a compass is placed in the vicinity of a current-carrying conductor, the needle aligns itself at right angles to the conductor. The north pole of the compass indicates the direction of the magnetic field produced by the current.
By knowing the direction of the current, you can use the left-hand rule for conductors to determine the direction of the magnetic lines of force.
Arrows are generally used in electrical diagrams to indicate the direction of current in a wire. A cross (+) on the end of a cross-sectional view of a wire indicates that the current is flowing away from you, while a dot (·) indicates that the current is flowing toward you.
When two adjacent parallel conductors carry current in the same direction, their magnetic fields oppose each other between the conductors and aid each other outside the conductors, producing attraction. When the currents flow in opposite directions, their magnetic fields aid each other between the conductors and oppose each other outside the conductors, producing repulsion.
MAGNETIC FIELDS
In 1819 Hans Christian Oersted, a Danish physicist, found that a definite relationship exists between magnetism and electricity. He discovered that an electric current is always accompanied by certain magnetic effects and that these effects obey definite laws.

MAGNETIC FIELD AROUND A CURRENT-CARRYING CONDUCTOR
If a compass is placed in the vicinity of a current-carrying conductor, the compass needle will align itself at right angles to the conductor, thus indicating the presence of a magnetic force. You can demonstrate the presence of this force by using the arrangement illustrated in the figure below.

In both (A) and (B) of the figure, current flows in a vertical conductor through a horizontal piece of cardboard. You can determine the direction of the magnetic force produced by the current by placing a compass at various points on the cardboard and noting the compass needle’s deflection. The direction of the magnetic force is assumed to be the direction in which the north pole of the compass points.
In Figure (A) below, the needle deflections show that a magnetic field exists in circular form around the conductor.

When the current flows upward (see Figure (A)), the field is clockwise when viewed from the top.
However, if you reverse the battery’s polarity so that the current flows downward (see Figure (B)), the field is counterclockwise.

The relation between the direction of the magnetic lines of force around a conductor and the direction of electron current flow in the conductor may be determined by employing the left-hand rule for a conductor

If you grasp the conductor in your left hand with the thumb extended in the direction of the electron flow (current) (− to +), your fingers will point in the direction of the magnetic lines of force.
Note that your fingers point in the direction that the north pole of the compass points when it is placed in the magnetic field surrounding the wire.
An arrow is generally used in electrical diagrams to denote the direction of current in a length of wire, as shown in Figure (A) to the left.

Where a cross-section of a wire is shown, an end view of the arrow is used.
Figure (B) illustrates a cross-sectional view of a conductor carrying current toward the observer.

Notice that the direction of the current is indicated by a dot, representing the head of the arrow.
A conductor that is carrying current away from the observer is illustrated in Figure (C).

Note that the direction of the current is indicated by a cross, representing the tail of the arrow. Also, note that the magnetic field around a current-carrying conductor is perpendicular to the conductor and that the magnetic lines of force are equal along all parts of the conductor.
When two adjacent parallel conductors are carrying current in the same direction, the magnetic lines of force combine and increase the strength of the field around the conductors, as shown in Figure (A) below.

This means that if two parallel and adjacent conductors are carrying currents in the same direction, the fields about the two conductors aid each other.
Two parallel conductors carrying currents in opposite directions are shown in Figure (B) below.

Note that the field around one conductor is opposite in direction to the field around the other conductor. The resulting lines of force oppose each other in the space between the wires, thus deforming the field around each conductor.
If the two conductors are carrying currents in opposite directions, the fields about the conductors repel each other.
MAGNETIC FIELD OF A COIL
When a wire is wound around a core, it forms a COIL.
The magnetic fields are produced when the currents in the coils combine. The combined influence of all the fields around the turns produces a two-pole field similar to that of a simple bar magnet. When the direction of current in the coil is reversed, the polarity of the two-pole field of the coil is reversed.
The figure to the left illustrates that when a straight wire is wound around a core, it forms a coil, and the magnetic field around the core takes on a different shape.

Figure (A) is a partial cutaway view showing the construction of a simple coil.
Figure (B) shows a cross-sectional view of the same coil.
Notice that the two ends of the coil are identified as X and Y.
The strength of the magnetic field of the coil is dependent upon:
- The number of turns of the wire in the coil.
- The amount of current in the coil.
- The ratio of the coil length to the coil width.
- The type of material in the core.
When the direction of the current in a coil is known, you can determine the magnetic polarity of the coil by using the Left-Hand Rule for Coils.
This rule is stated as follows:

Grasp the coil in your left hand with your fingers “wrapped around” in the direction of the electron current flow. Your thumb will then point toward the north pole of the coil.
STRENGHT OF AN ELECTROMAGNETIC FIELD
The strength or intensity of a coil’s magnetic field depends on several factors. The main ones are listed below and will be discussed again later.
- The number of turns of wire in the coil
- The amount of current flowing in the coil.
- The ratio of the coil length to the coil width.
- The type of material in the core.
LOSSES IN AN ELECRTROMAGNETIC FIELD
When current flows through a conductor, moving electric charge produces a magnetic field around the conductor. When the current reverses direction, the magnetic field also reverses direction.
In equipment that uses iron or other ferromagnetic core materials, the reversing magnetic field causes the magnetic domains in the core to realign continually. Energy is required to reverse this magnetization, and some of that energy is converted into heat. This power loss is called hysteresis loss.
Hysteresis loss is most significant in AC devices with magnetic cores, such as motors, generators, and transformers. When we discuss these devices later in this lesson, we will cover hysteresis loss in more detail.bASIC
BASIC AC GENERATION
From the previous discussion, you learned that a current-carrying conductor produces a magnetic field around itself.
Under-producing a voltage (EMF) using magnetism, you learned how a changing magnetic field produces an EMF in a conductor. That is, if a conductor is placed in a magnetic field, and either the field or the conductor moves, an EMF is induced in the conductor.
This effect is called electromagnetic induction.
CYCLE
The figure below shows a suspended loop of wire (conductor) being rotated (moved) clockwise through the magnetic field between the poles of a permanent magnet.
For ease of explanation, the loop has been divided into a blue half and a brown half.

Notice in (A) of the figure that the dark half is moving along (parallel to) the lines of force.
Consequently, it is cutting NO lines of force. The same is true of the light half, which is moving in the opposite direction. Since the conductors cut no lines of force, no EMF is induced.
As the loop rotates toward the position shown in (B), it cuts more and more lines of force per second (inducing an ever-increasing voltage) because it is cutting more directly across the field (lines of force).
At (B), the conductor is shown completing one-quarter of a complete revolution, or 90º, of a complete circle.
Because the conductor is now cutting directly across the field, the voltage induced in the conductor is maximum.
When the value of induced voltage at various points during the rotation from (A) to (B) is plotted on a graph (and the points connected), a curve appears as shown below.
As the loop continues to be rotated toward the position shown below in (C), it cuts fewer and fewer lines of force.
The induced voltage decreases from its peak value.
Eventually, the loop is once again moving in a plane parallel to the magnetic field, and no EMF is induced in the conductor.
The loop has now been rotated through half a circle (one alternation or 180º). If the preceding quarter-cycle is plotted, it appears as shown above.
When the same procedure is applied to the second half of the rotation (180º through 360º), the curve appears as shown above.
Notice the only difference is in the polarity of the induced voltage. Where previously the polarity was positive, it is now negative. The sine curve shows the induced voltage at each instant of time during the loop’s rotation.
Notice that this curve contains 360º, or two alternations.
Two alternations represent one complete cycle of rotation.
Assuming a closed path is provided across the ends of the conductor loop, you can determine the direction of current in the loop by using the left-hand rule for generators.

First, place your left hand on the illustration with the fingers as shown.
Your THUMB will now point in the direction of rotation (relative movement of the wire to the magnetic field); your
FOREFINGER will point in the direction of magnetic flux (north to south); and your MIDDLE FINGER (pointing out of the paper) will point in the direction of electron current flow.
By applying the left-hand rule to the dark half of the loop in (B) of the figure above, you will find that the current flows in the direction indicated by the heavy arrow.
Similarly, by using the left-hand rule on the light half of the loop, you will find that the current therein flows in the opposite direction.
The two induced voltages in the loop add to form a single total EMF. This EMF drives the current in the loop.
When the loop rotates to the position shown in (D) of the previous Figure, the action reverses. The dark half is moving up instead of down, and the light half is moving down instead of up.
By applying the left-hand rule once again, you will see that the total induced emf and its resulting current have reversed direction. The voltage builds up to maximum in this new direction, as shown by the sine curve.
The loop finally returns to its original position (E), at which point the voltage is again zero. The sine curve represents one complete cycle of voltage generated by the rotating loop.
All the illustrations in this chapter show the wire loop moving clockwise. In actual practice, the loop can be moved clockwise or counterclockwise.
Regardless of the direction of movement, the left-hand rule applies.
If the loop is rotated through 360º at a steady rate, and if the strength of the magnetic field is uniform, the voltage produced is a sine wave. Continuous rotation of the loop will produce a series of sine-wave voltage cycles or, in other words, an AC voltage.
As mentioned previously, the cycle consists of two complete alternations in a period.
The Hertz (Hz) is the unit of frequency, equal to one cycle per second. If one cycle per second is one hertz, then 100 cycles per second are equal to 100 hertz, and so on.
Throughout these modules, the term cycle is used when no specific time element is involved, and the term Hertz (Hz) is used when the time element is measured in seconds.
FREQUENCY
If the loop in the previous figure (A) makes one complete revolution each second, the generator produces one complete cycle of AC during each second (1 Hz).
Increasing the number of revolutions to two per second will produce two complete cycles of AC per second (2 Hz).
The number of complete cycles of alternating current or voltage per second is called the frequency.
Frequency is always measured and expressed in hertz.
Alternating-current frequency is an important concept to understand, as most AC electrical equipment requires a specific frequency to operate properly.
PERIOD
The time required to complete one cycle of a waveform is called the Period Of The Wave.

An individual cycle of any sine wave represents a definite amount of time.
Notice that the figure below shows 2 cycles of a sine wave with a frequency of 2 hertz (Hz).

Since 2 cycles occur each second, one cycle of a waveform is called the period of the wave.
The period is one-half second.
The formula indicates the relationship between time (t) and frequency (f).
![]()
Where: t = period in seconds and f = Frequency in hertz
- Each cycle of the sine wave shown in the figure above consists of two identically shaped variations in voltage.
- The variation that occurs while the voltage is positive is called the Positive Alternation.
- The variation that occurs while the voltage is negative is called the Negative Alternation.
- In a sine wave, these two alternations are identical in size and shape but opposite in polarity.
- The distance from zero to the maximum value of each alternation is called the Amplitude.
- The amplitude of the positive alternation and the amplitude of the negative alternation are the same.
WAVELENGHT
The time it takes for a sine wave to complete one cycle is defined as the period of the waveform.
The distance the sine wave travels over one cycle is called its wavelength. Wavelength, indicated by the symbol λ (Greek lambda), is the distance along the waveform from one point to the same point on the next cycle.
You can observe this relationship by examining the figure below.

The point on the waveform at which wavelength measurement begins is not important, as long as the distance is measured to the same point on the next cycle.

ALTERNATING CURRENT VALUES
When discussing alternating current and voltage, you will often need to express them in terms of maximum (peak) values, peak-to-peak values, effective values, average values, or instantaneous values.
Each value has a different meaning and describes a different amount of current or voltage.
PEAK AND PEAK-TO-PEAK VALUES: Refer to the figure below. Notice that it shows the positive alternation of a sine wave (a half-cycle of AC) and a DC waveform occurring simultaneously.

Note that the DC starts and stops at the same moment, as does the positive alternation, and that both waveforms rise to the same maximum value.
However, the DC values are greater than the corresponding AC values at all points except the point at which the positive alternation passes through its maximum value.
At this point, the DC and AC values are equal. This point on the sine wave is called the maximum or peak value.
During each complete cycle of AC, there are always two maximum or peak values, one for the positive half-cycle and the other for the negative half-cycle.
The difference between the peak positive value and the peak negative value is called the peak-to-peak value of the sine wave.
This value is twice the maximum (peak) value of the sine wave and is sometimes used to measure AC voltages. Note the difference between peak and peak-to-peak values

Usually, alternating voltage and current are expressed in Effective Values (a term you will study later) rather than in peak-to-peak values.
INSTANTANIOUS VALUES
The instantaneous value of an alternating voltage or current is the value of the voltage or current at a given instant. The value may be zero if the instant is when the voltage polarity changes.
It may also equal the peak value if the selected instant occurs when the voltage or current stops increasing and starts decreasing.
There are an infinite number of instantaneous values between zero and the peak value.
AVERAGE VALUE
The average value of an alternating current or voltage is the average of all the instantaneous values during one alternation.
Since the voltage increases from zero to its peak value and then decreases back to zero during one alternation, the average value must lie between those two limits.
You could determine the average value by adding a series of instantaneous values over one alternation (between 0º and 180º) and then dividing the sum by the number of instantaneous values used.
The computation shows that the average value of one cycle of a sine wave is 0.636 times its peak value.
The formula for average voltage is Eavg = 0.636 × Emax, where Eavg is the average voltage of one alternation, and Emax is the maximum or peak voltage.
Similarly, the formula for average current is Iavg = 0.636 × Imax, where Iavg is the average current over one alternation, and Imax is the peak current.
Do not confuse the above definition of an average value with that of the average value of a complete cycle.
Because the voltage is positive during one alternation and negative during the other, the average voltage over a complete cycle is zero.
EFFECTIVE VALUE OF A SINE WAVE
Emax, Eavg, Imax, and Iavg are values used in AC measurements.
Another value used is the effective AC value; this is the alternating voltage or current value that would have the same effect on a given resistance as a comparable direct voltage or current would.
In an earlier discussion, you were told that when current flows through a resistance, it produces heat. When direct current flows through a resistance, the amount of electrical power converted into heat equals I2R watts.
However, since an alternating current with a maximum value of 1 ampere does not maintain a constant value, the alternating current will not produce as much heat in the resistance as produced by a direct current of 1 ampere.
A sinusoidal alternating current with a maximum, or peak, value of 1 ampere does not produce the same heating effect as 1 ampere of direct current. The effective, or RMS, value of a sine-wave AC is 0.707 times its maximum value. Therefore, an AC sine wave with a peak value of 1 ampere has an effective value of 0.707 ampere.
Since heating is proportional to the square of the current, this 1-ampere peak AC produces the same heating effect as 0.707 ampere DC. Compared with 1-ampere DC, it produces only 50 percent as much heat.
Conversely, an AC sine wave must have an RMS value of 1 ampere, and therefore a peak value of approximately 1.414 amperes, to produce the same heating effect as 1 ampere DC.
Mathematically,
![]()
Therefore, for the effective value of AC (Ieff) = 0.707 × Imax.
The rate at which heat is produced in a resistor provides a convenient basis for determining the effective value of alternating current, a method known as the “heating effect” method.
An alternating current is said to have an effective value of one ampere when it produces heat in a given resistance at the same rate as one ampere of direct current.
You can compute the effective value of a sine wave of current to a fair degree of accuracy by taking equally spaced instantaneous values of current along the curve and extracting the square root of the average of the sum of the squared values.
For this reason, the effective value is often referred to as the “root-mean-square” (RMS) value.
Thus,
![]()
(Symbol for Sum = Sigma)
Stated another way, the effective or RMS value (Ieff) of a sine wave of current is 0.707 times the maximum value of current (Imax).
Thus, Ieff = 0.707 × Imax. When Ieff is known, you can find Imax by using the formula Imax = 1.414 × Ieff.
You might wonder where the constant 1.414 comes from. To find out, examine the figure above again and read the following explanation.
Assume that the DC in Figure (A) above is maintained at 1 ampere and the resistor temperature at 100º C. Also, assume that the AC in Figure (B) is increased until the resistor’s temperature reaches 100ºC.
At this point, a maximum AC value of 1.414 amperes is required to produce the same heating effect as direct current. Therefore, in the AC circuit, the maximum current required is 1.414 times the effective current.
Remember the above relationship, and that the effective value (Ieff) of any sine-wave current is always 0.707 times the maximum value (Imax).
Since alternating current is caused by an alternating voltage, the ratio of the effective value of voltage to the maximum value of voltage is the same as the ratio of the effective value of current to the maximum value of current.
Stated another way, the effective or RMS value (Eeff) of a sine wave of voltage is 0.707 times the maximum value of voltage (Emax)
Given:
Es = 120 V
Emax = 30 A
Solution:
Emax = 1.414 X Eeff
Emax = 1.414 X 120 V
Emax = 169.68 V
Ieff = 0.707 X Imax
Ieff = 0.707 X 30 A
Ieff = 21.21 A
The figure to the right shows the relationship between the various values used to indicate sine-wave amplitude.

Review the values in the figure below to ensure you understand what each value indicates.
SINE WAVE IN PHASE
When a sine wave of voltage is applied to a resistance, the resulting current is also a sine wave,
this follows Ohm’s law, which states that current is directly proportional to the applied voltage.
Now examine the figure below.

Notice that the sine wave of voltage and the resulting sine wave of current are superimposed on the same time axis.
Also, notice that as the voltage increases in the positive direction, the current increases, and that when the voltage reverses, the current reverses.
When two sine waves are precisely in step with one another, they are said to be In Phase. To be in phase, the two sine waves must go through their maximum and minimum points at the same time and in the same direction.
SINE WAVES OUT OF PHASE
When two sine waves go through their minimum and maximum points at different times, a phase difference exists between them.
The figure to the right shows a voltage wave E-1, which is considered to start at 0º (time one).
As voltage wave E1 reaches its positive peak, voltage wave E2 starts its rise (time two).
Because these voltage waves do not reach their maximum and minimum points at the same instant, a phase difference exists between them.
The two waves are out of phase. For these two waves, the phase difference is 90º.
To further describe the phase relationship between two sine waves, the terms lead and lag are used. The amount by which one sine wave leads or lags another sine wave is measured in degrees.
Refer to the figure above. Observe that wave E2 starts 90º later than wave E1.
You can also describe this relationship by saying that wave E1 leads wave E2 by 90º, or that wave E2 lags wave E1 by 90º (Either statement is correct; it is the phase relationship between the two sine waves that is important.)
One sine wave can lead or lag another sine wave by any number of degrees, except 0º or 360º. When the latter condition exists, the two waves are said to be in phase.
Thus, two sine waves that differ in phase by 45º are out of phase with each other, whereas two sine waves that differ in phase by 360º are in phase with each other.
A common phase relationship is shown in the figure below. Notice that the two waves illustrated differ in phase by 180º.
Notice also that although the waves pass through their maximum and minimum values at the same time, their instantaneous voltages are always of opposite polarity.
If two such waves exist across the same component, and the waves are of equal amplitude, they cancel each other.
When they have different amplitudes, the resultant wave has the same polarity as the larger wave and has an amplitude equal to the difference between the amplitudes of the two waves.
To determine the phase difference between two sine waves, locate the points on the time axis where the two waves cross the time axis traveling in the same direction.
The number of degrees between the crossing points is the phase difference.
The wave that crosses the axis at a later time (to the right on the time axis) is said to lag the other wave.
OHM’S LAW IN AC CIRCUITS
Many AC circuits contain resistance only. The rules for these circuits are the same as those for DC circuits.
Resistors, lamps, and heating elements are examples of resistive elements.
When an AC circuit contains only resistance, Ohm’s Law, Kirchhoff’s Law, and the various rules that apply to voltage, current, and power in a DC circuit also apply to the AC circuit.

The Ohm’s Law formula for an AC circuit can be stated as
![]()
or
![]()
Remember, unless otherwise stated, all AC voltages and current values are given as effective values.
The formula for Ohm’s Law can also be stated as
![]()
or
![]()
or
![]()
The important thing to keep in mind is: Do not mix AC values.
When you solve for effective values, all values you use in the formula must be effective values.
Similarly, when you solve for average values, all values you use must be average values. This point should be clearer after you work on the following problem:
Example problem:
A series circuit consists of two resistors (R1 = 5 ohms and R2 = 15 ohms) and an alternating voltage source of 120 volts. What is Iavg?
Given:
R1 = 5 ohms
R2 = 15 ohms
Solution:
First, solve for the total resistance RT
RT = R1 + R2
RT = 5 ohms + 15 ohms
RT = 20 ohms
The alternating voltage is assumed to be an effective value (since it is not specified to be otherwise).
Apply Ohm’s Law Formula:
![]()
![]()
![]()
You can now find Iavg.
Substitute 8.484 amperes into the Iavg formula and solve for Iavg.
Iavg = 0.636 X Imax
Iavg = 0.636 X 8.484 A
Iavg = 5.4 A (rounded off to one decimal point)
Remember, you can use Ohm’s Law formulas to solve any purely resistive AC circuit problem. Use the formulas in the same manner as you would solve a DC circuit problem.
INDUCTANCE
Inductance is the property of a coil that causes energy to be stored in a magnetic field about the coil. This stored energy opposes any change in current.
The study of inductance is a challenging but rewarding segment of electricity. It is challenging because at first, it seems that new concepts are being introduced. However, these new concepts are merely extensions of fundamental principles already covered in this course.
The study of inductance is rewarding because a thorough understanding of it will enable you to acquire a working knowledge of electrical circuits more rapidly.
This lesson defines inductance and describes the factors that affect it.
CHARACTERISTICS OF INDUCTANCE
Inductance is the characteristic of an electrical circuit that opposes the starting, stopping, or change in value of current.
- The symbol for inductance is L.
- The basic unit of inductance is the henry (H).
One Henry equals the inductance required to induce 1 volt in an inductor by a change of current of 1 ampere per second.
An analogy for inductance is pushing a heavy load (such as a wheelbarrow or a car). It takes more work to get the load moving than to keep it moving.
Once the load starts to move, it is easier to keep it moving than to stop it again, because it possesses inertia.
Inertia is the characteristic of mass that opposes a change in velocity.
Inductance has the same effect on current in an electrical circuit as inertia has when moving a mechanical object. It takes more energy to start or stop the current than to keep it flowing.
ELECTROMOTIVE FORCE
Electromotive force is developed whenever there is relative motion between a magnetic field and a conductor.

Electromotive force is the difference in potential or voltage that exists between two points in an electrical circuit.
In generators and inductors, the EMF is developed by the action between the magnetic field and the electrons in a conductor.
The figure below shows that an inductor is a coiled wire (such as in a relay coil, motor, or transformer), illustrating the EMF generated in an electrical conductor.

When a magnetic field moves through a stationary metallic conductor, electrons are dislodged from their orbits. The electrons move in a direction determined by the motion of the magnetic field lines, as shown below:

The difference between the charges in the conductor equals the difference in potential (or voltage).
This voltage, caused by a moving magnetic field, is called electromotive force (EMF).
In simple terms, the action of a moving magnetic field on a conductor can be compared to the action of a broom.
Consider the moving magnetic field to be a moving broom.

As the magnetic broom moves along (through) the conductor, it gathers up and pushes electrons before it, as shown below:
The area from which electrons are moved becomes positively charged, while the area into which electrons are moved becomes negatively charged.
The potential difference between these two areas is the electromotive force (EMF).
SELF-INDUCTANCE
Even a perfectly straight length of conductor has some inductance.
As you know, current in a conductor produces a magnetic field surrounding the conductor.
When the current changes, the magnetic field changes, causing relative motion between the magnetic field and the conductor and inducing an electromotive force (EMF) in the conductor.
This EMF is called a Self-Induced EMF because it is induced in the conductor carrying the current.
The EMF produced by this moving magnetic field is also referred to as Counter Electromotive Force (CEMF).
To understand what CEMF is and how it develops, first review the basic requirements for producing voltage.
To produce a voltage or EMF magnetically, there must be the following:
- A conductor.
- A magnetic field.
- Relative motion.
Next, review some of the properties of an electrical circuit.
DO NOT connect the ends of a length of wire to a terminal of an AC generator; this will cause an electrical short at the point where the maximum current flows.
Excessive current would flow because the wire would offer only minimal resistance, allowing it to flow; this would damage the electrical system.
The polarity of the counter-electromotive force is in the opposite direction to the applied voltage of the conductor.
The overall effect opposes a change in current magnitude.
This effect is summarized by Lenz’s law, which states:
Lenz’s Law – The induced EMF in any circuit is always in a direction to oppose the effect that produced it
If the shape of the conductor is changed to form a loop, then the electromagnetic field around each portion of the conductor cuts across some other portion of the same conductor. This is shown in its simplest form in the figure below.
The length of the conductor is looped so that two portions of the conductor lie next to each other. These portions are labeled Conductor 1 and Conductor 2.
When the switch is closed, the current (electron flow) in the conductor produces a magnetic field around the entire conductor. For simplicity, the magnetic field (indicated by expanding lines of flux) is shown in a single plane perpendicular to both conductors.
Although the expanding field of flux originates at the same time in both conductors, it is considered to originate in conductor 1, and its effect on conductor 2 will be explained.
As the current increases, the flux field expands outward from conductor 1, cutting across a portion of conductor 2. This results in an induced EMF in conductor 2, as shown by the dashed arrow.
Note that the induced emf is in the opposite direction to (in opposition to) the battery current and voltage, as stated in Lenz’s law.
The direction of this induced voltage may be determined by applying the Left-Hand Rule for Generators. This rule is applied to a portion of conductor 2 that is “lifted” and enlarged for this purpose in Figure (A).

This rule states that if you point the thumb of your left hand in the direction of the relative motion of the conductor and your index finger in the direction of the magnetic field, your middle finger, extended as shown, will now indicate the direction of the induced current, which will generate the induced voltage (CEMF) as shown.
In Figure (B), the same section of conductor 2 is shown after the switch has been opened. The flux field is collapsing.
Applying the left-hand rule in this case shows that the reversal of flux movement has caused a reversal in the direction of the induced voltage. The induced voltage is now in the same direction as the battery voltage.
The most important point to note is that the self-induced voltage opposes both changes in current. That is, when the switch is closed, this voltage delays the initial current rise by opposing the battery voltage.
When the switch is open, it keeps the current flowing in the same direction by helping maintain the battery voltage. Thus, as the current builds up, it produces an expanding magnetic field.
This field induces an EMF in the direction opposite to the actual current flow.
This induced EMF opposes the growth of both the current and the magnetic field. If the increasing current had not set up a magnetic field, there would have been no opposition to its growth.
The whole reaction, or opposition, is caused by the creation or collapse of the magnetic field, the lines of which, as they expand or contract, cut across the conductor and develop the counter EMF.
Since all circuits have conductors in them, you can assume that all circuits have inductance. However, inductance has its greatest effect only when the current changes.
Inductance does not oppose the current; it only opposes a change in the current. When the current is constantly changing, as in an AC circuit, inductance has a greater effect.
To increase inductance, you can form the conductor into a loop or coil. A coil is also called an inductor.
The figure below shows a conductor coiled.

A current through a loop produces a magnetic field that encircles the loop in the direction shown in Figure (A).
As the current increases, the magnetic field expands and cuts all the loops as shown in Figure (B).
The current in each loop affects all other loops.
The field cutting the other loop increases opposition to a change in current.
Inductors are classified according to core type.
- The core is the center of the inductor, just as the core of an apple is the center of an apple.
- The inductor is made by forming a coil of wire around a core.
- The core material is normally one of two basic types: soft iron or air.
Iron Core
An iron-core inductor and its schematic symbol (which is represented with lines across the top of it to indicate the presence of an iron core) are shown in Figure A.

Air Core
The air-core inductor may be nothing more than a coil of wire, but it is usually a coil formed around a hollow form of some nonmagnetic material, such as cardboard.
This material serves no purpose other than to hold the shape of the coil. An air-core inductor and its schematic symbol are shown in Figure (B)

FACTORS AFFECTING COIL INDUCTANCE
Several physical factors affect a coil’s inductance.
They include the number of turns in the coil, the coil diameter, the coil length, the core material, and the number of winding layers.
Inductance depends entirely upon the physical construction of the circuit and can only be measured with special laboratory instruments.
Of the factors mentioned, consider first how the number of turns affects a coil’s inductance.
Figures (A) and (B) below show two coils.
Coil (A) has two turns. In coil (A), the flux field set up by one loop cuts through another loop.

Coil (B) has four turns. In coil (B), the flux field set up by one loop cuts three other loops.

Doubling the number of turns in the coil will produce a field twice as strong for the same current.
A field twice as strong, cutting twice as many turns, will induce four times the voltage. Therefore, it can be said that the inductance varies as the square of the number of turns.
The second factor is the coil diameter.
In the figure below, you can see that the coil in view B has twice the diameter of the coil in view A.

Physically, it requires more wire to construct a coil of a large diameter than one of a small diameter with an equal number of turns.
Therefore, more lines of force exist to induce a counter-emf in the coil with the larger diameter.
The inductance of a coil increases directly as the cross-sectional area of the core increases. Recall the formula for the area of a circle: A = πr2.
Doubling the radius of a coil increases the inductance by a factor of four.
The third factor affecting a coil’s inductance is its length. Figure (A) and (B) shows two examples of coil spacing.
Coil (A) has three turns, spaced widely, making a relatively long coil. A coil of this type has few flux linkages, due to the greater distance between each turn.
Therefore, coil (A) has a relatively low inductance. Coil (B) has closely spaced turns, making a relatively short coil.

This close spacing increases the flux linkage and, in turn, the coil’s inductance. Doubling the length of a coil while keeping the same number of turns halves its inductance.
The fourth physical factor is the type of core material used with the coil. The figure below shows two coils:
Coil (A) with an air core, and coil (B) with a soft-iron core. The magnetic core of coil (B) is a better path for magnetic lines of force than the nonmagnetic core of coil (A).

The soft-iron magnetic core’s high permeability has less reluctance to the magnetic flux, resulting in more magnetic lines of force.
This increase in magnetic lines of force increases the number of lines cutting through each loop of the coil, thereby increasing the coil’s inductance.
It should now be apparent that the inductance of a coil increases directly as the permeability of the core material increases.
Another way to increase inductance is to wind the coil in layers. The figure below shows three cores with different amounts of layering.

The coil in Figure (A) is a poor inductor compared to the others because its turns are widely spaced and there is no layering.
The flux movement, indicated by the dashed arrows, does not link effectively because there is only one layer of turns.
Figure (B) shows a more inductive coil. The turns are closely spaced, and the wire has been wound in two layers. More flux loops link the two layers during all flux movements.
Note that nearly all the turns, such as X, are next to four other turns (shaded), which increases the flux linkage.
A coil can be made still more inductive by winding it in three layers, as shown in Figure (C).
The increased number of layers (cross-sectional area) further improves flux linkage.
Note that some turns, such as Y, lie directly next to six other turns (shaded). In actual practice, layering can continue through many more layers.
The important fact to remember, however, is that the coil’s inductance increases with each added layer.
As you have seen, several factors can affect a coil’s inductance, and all of them are variable. Many differently constructed coils can have the same inductance.
The important point to remember, however, is that inductance depends on the degree of coupling between the wire conductor(s) and the electromagnetic field. In a straight-length conductor, there is very little flux linkage between one part of the conductor and another.
Therefore, its inductance is extremely small. It has been shown that conductors become much more inductive when wound into coils. This is because the conductor turns lie side by side in the coil, maximizing flux linkage between them.
UNIT OF INDUCTANCE
As stated before, the basic unit of inductance (L) is the HENRY (H), named after Joseph Henry, the co-discoverer with Faraday of the principle of electromagnetic induction.
An inductor has an inductance of 1 Henry if an emf of 1 volt is induced in the inductor when the current through the inductor is changing at the rate of 1 ampere per second.
The relationship between the induced voltage, the inductance, and the rate of change of current with respect to time is stated mathematically as:
![]()
Where ( Eind ) is the induced EMF in volts, (L) is the inductance in henrys, and ( ΔI ) is the change in current in amperes occurring in ( Δt )seconds.
The symbol (Δ) (Greek letter delta) means “a change in ….”.
The Henry is a large unit of inductance and is used with relatively large inductors. With small inductors, millihenry is used.
(A millihenry is equal to 1 × 10-3 henry, and one henry is equal to 1,000 millihenrys.)
For still smaller inductors, the unit of inductance is the microhenry (μH).
(A μH = 1 × 10 -6H, and one henry is equal to 1,000,000 microhenrys.)
GROWTH AND DECAY OF CURRENT IN AN LR SERIES CIRCUIT
When a battery is connected across a “pure” inductor, the current builds up to its final value at a rate determined by the battery voltage and its internal resistance.
The current buildup is gradual because the coil’s self-inductance generates a counter-EMF. When the current starts to flow, the magnetic lines of force move outward from the coil.
These lines cut the turns of wire in the inductor, inducing a counter-EMF that opposes the battery’s EMF.
This opposition delays the time to the steady state. When the battery is disconnected, the lines of force collapse.
Again, these lines cut the inductor’s turns, inducing an emf that tends to prolong the current flow.
A voltage divider containing resistance and inductance may be connected in a circuit utilizing a special switch, as shown in Figure (A) below.

Such a series arrangement is called an LR series circuit.
When switch S1 is closed (as shown), a voltage ES appears across the voltage divider.
At this instant, the current will attempt to increase to its maximum value.
However, this instantaneous change in current causes coil L to produce a back EMF of opposite polarity and nearly equal in magnitude to the source EMF.
This back-EMF opposes the rapid change in current.
Figure (B) shows that at the instant of switch S1 closing, there is no measurable growth current (ig), a minimum voltage drop across resistor R, and a maximum voltage across inductor L.

Because the voltage across the inductor (L) decreases, the growth current (ig) increases and, consequently, er increases.
Figure (B) shows that the voltage across the inductor (eL) finally becomes zero when the growth current (ig) stops increasing, while the voltage across the resistor (eR) builds up to a value equal to the source voltage (ES).
Electrical inductance is like mechanical inertia, and the growth of current in an inductive circuit can be likened to the acceleration of a boat on the water.
The boat does not move the instant a constant force is applied. At this instant, all the applied force is used to overcome the inertia of the boat.
Once the inertia is overcome, the boat will start to move.
After a while, the boat’s speed reaches its maximum, and the applied force is used to overcome the friction between the water and the hull.
When the battery switch (S1) in the LR circuit of Figure (A) is closed, the rate of current increase is maximum in the inductive circuit.
At this instant, all the battery voltage is used to overcome the EMF of self-induction, which is at its maximum because the rate of change of current is at its maximum.
Thus, the battery voltage equals the inductor drop, and the voltage across the resistor is zero.
As time goes on, more of the battery voltage appears across the resistor and less across the inductor.
The rate of change of current decreases, and the induced EMF decreases. As the current approaches steady state, the drop across the inductor approaches zero, and all the battery voltage is “dropped” across the circuit’s resistance.
Thus, the voltages across the inductor and the resistor change in magnitude during the period of current growth, just as the force applied to the boat divides itself between the effects of inertia and friction.
In both examples, the force is first developed across the inertia/inductive effect and, finally, across the friction/resistive effect.
Figure (C) shows that when switch S2 is closed (source voltage ES removed from the circuit), the flux that has been established around the inductor (L) collapses through the windings, which induces a voltage eL in the inductor, with polarity opposite to ES and of equal magnitude.

The induced voltage causes the decay current (id) to flow through resistor R in the same direction as the original current (when S1 was closed).
A voltage (eR) initially equal to the source voltage (ES) develops across R.
The voltage across the resistor (eR) rapidly falls to zero, as does the voltage across the inductor (eL), because the flux collapses.
Just as the example of the boat was used to explain the growth of current in a circuit, it can also be used to explain the decay of current in a circuit.
When the force acting on the boat is removed, the boat continues to move through the water for a while before coming to a stop. This is because energy was stored in the boat’s inertia. After a period, the friction of the water overcomes the inertia of the boat, and the boat stops moving.
Just as the inertia of the boat stores energy, the magnetic field of an inductor stores energy.
Because of this, even when the power source is removed, the stored energy in the inductor’s magnetic field tends to keep current flowing in the circuit until the magnetic field collapses.
L/R TIME CONSTANT
In a series circuit containing a resistor (R1) and an inductor (L1), what voltage exists across R1 when the counter emf is at its maximum value?
What happens to the voltage across the resistance in an LR circuit during current buildup in the circuit, and during current decay in the circuit?
The L/R Time Constant is a valuable tool for determining the time required for the current in an inductor to reach a specific value.

As shown in the figure below, one L/R time constant is the time required for the current in an inductor to increase to 63 percent (63.2 percent) of the maximum current.
Each time constant is equal to the time required for the current to increase by 63.2 percent of the difference in value between the current flowing in the inductor and the maximum current.
Maximum current flows in the inductor after five L/R time constants have elapsed.
The following example should clear up any confusion about time constants. Assume that the maximum current in an LR circuit is 10 amperes. As you know, when the circuit is energized, it takes time for the current to go from zero to 10 amperes.
When the first time constant is reached, the current in the circuit is 63.2% of 10 amperes. Thus, the current amplitude after 1 time constant is 6.32 amperes.
During the second time constant, the current again increases by 63.2% (.632) of the difference in value between the current flowing in the inductor and the maximum current.
This difference is 10 amperes minus 6.32 amperes and equals 3.68 amperes; 63.2% of 3.68 amperes is 2.32 amperes. This increase in current during the second time constant is added to the current from the first time constant. Thus, upon completion of the second time constant, the amount of current in the LR circuit is 6.32 amperes + 2.32 amperes = 8.64 amperes.
During the third time constant, the current again increases:
10 amperes – 8.64 amperes = 1.36 amperes
1.36 amperes x .632 = 0.860
8.64 amperes + 0.860 amperes = 9.50 amperes
During the fourth time constant, the current again increases:
10 amperes – 9.50 amperes = 0.5 amperes
0.5 amperes x .632 = 0.316
9.50 amperes + 0.316 amperes = 9.82 amperes
During the fifth time constant, the current increases as before:
10 amperes – 9.82 amperes = 0.18 amperes
0.18 amperes x .632 = 0.114
9.82 amperes + 0.114 amperes = 9.93 amperes
Thus, the current at the end of the fifth time constant is almost equal to 10.0 amperes, the maximum current. For all practical purposes, the slight difference in value can be ignored.
When an LR circuit is de-energized, the circuit current decreases (decays) to zero in five time constants at the same rate that it previously increased. If the growth and decay of current in an LR circuit are plotted on a graph, the curve appears as shown in the figure above.
Notice that the current increases and decays at the same rate in five time constants. The time constant, in seconds, is equal to the inductance in henrys divided by the circuit resistance in ohms.
The formula used to calculate one L/R time constant is:
![]()
POWER LOSS IN AN INDUCTOR
Since an inductor (coil) consists of a few turns of wire, and since all wires have some resistance, every inductor has a certain amount of resistance. Normally, this resistance is small.
It is usually neglected when solving various types of AC circuit problems because the inductor’s reactance (the opposition to alternating current, which will be discussed later) is much greater than the resistance, so the resistance has a negligible effect on the current.
However, since some inductors are designed to carry relatively large amounts of current, considerable power can be dissipated in the inductor even though the amount of resistance in the inductor is small.
This wasted power is called Copper Loss. The copper loss of an inductor can be calculated by multiplying the square of the current in the inductor by the resistance of the winding (I2R). In addition to copper loss, an iron-core coil (inductor) has two types of iron loss.
These are called Hysteresis Loss and Eddy-Current Loss.
Hysteresis loss is the power consumed as the inductor’s magnetic field reverses each time the current direction changes.
Eddy-current loss is due to the heating of the core by circulating currents that are induced in the iron core by the magnetic field around the turns of the coil. All these losses dissipate power as heat. Since this power cannot be returned to the electrical circuit, it is lost power.
MUTUAL INDUCTANCE
Whenever two coils are located so that the flux from one coil links with the turns of the other coil, a change in flux in one coil induces an EMF in the other coil. This allows energy from one coil to be transferred, or coupled, to the other coil.
The two coils are said to be coupled or linked by the property of Mutual Inductance (M). The amount of mutual inductance depends on the relative positions of the two coils. This is shown below.

(A) If the coils are close together so that nearly all the flux of one coil links the turns of the other, the mutual inductance is high.
(B) If the coils are separated by a considerable distance, the amount of flux common to both coils is small, and the mutual inductance is low.
Conversely, (C) the mutual inductance can be increased greatly by mounting the coils on a common iron core.
Two coils are placed close together as shown in the figure below.

Coil 1 is connected to a battery through switch S, and coil 2 is connected to an ammeter (A).
When switch S is closed, as in figure (A), the current that flows in coil 1 sets up a magnetic field that links with coil 2, causing an induced voltage in coil 2 and a momentary deflection of the ammeter.
When the current in coil 1 reaches a steady value, the ammeter returns to zero.
If switch S is now opened as in figure (B), the ammeter (A) deflects momentarily in the opposite direction, indicating a momentary flow of current in the opposite direction in coil 2.
The collapsing magnetic field of coil 1 produces this current in coil 2.
FACTORS AFFECTING MUTUAL INDUCTANCE
The mutual inductance of two adjacent coils is dependent upon the physical dimensions of the two coils, the number of turns in each coil, the distance between the two coils, the relative positions of the axes of the two coils, and the permeability of the cores.
The Coefficient Of Coupling between two coils is equal to the ratio of the flux cutting one coil to the flux originating in the other coil.
If the two coils are positioned with respect to each other so that all the flux of one coil cuts all the turns of the other, the coils are said to have a unity coefficient of coupling. It is never exactly equal to unity (1), but it approaches this value in certain types of coupling devices. If all the flux produced by one coil cuts only half the turns of the other coil, the coefficient of coupling is 0.5.
The coefficient of coupling is designated by the letter K. The mutual inductance between two coils, L1 and L2, is expressed in terms of the inductance of each coil and the coefficient of coupling K.
As a formula:
![]()
Where:
M = Mutual inductance in Henrys
K = Coefficient of couplings
L1, L2 = Inductance of the coils in Henrys
Example problem: One 10-H coil and one 20-H coil are connected in series and are physically close enough to each other so that their coefficient of coupling is 0.5.
What is the mutual inductance between the coils?
Use the formula:
![]()
Solution:
![]()
![]()
![]()
![]()
SERIES INDUCTORS WITHOUT MAGNETIC COUPLING
When inductors are well-shielded or are located far enough apart from one another, the effect of mutual inductance is negligible.
If there is no mutual inductance (magnetic coupling) and the inductors are connected in series, the total inductance is equal to the sum of the individual inductances.
As a formula:
LT = L1 + L2 + L3 +…Ln
where LT is the total inductance; L1, L2, L3 are the inductances of L1, L2, L3; and Ln means that any number (n) of inductors may be used.
The inductances of inductors in series are added together like the resistances of resistors in series.
SERIES INDUCTORS WITH MAGNETIC COUPLING
When two inductors in series are so arranged that the field of one links the other, the combined inductance is determined as follows: LT = L1 + L2 ± 2M
Where:
LT = The total inductance
L1 L2 = The inductance of L1 L2
M = The mutual inductance between the two inductors
The factor 2M accounts for the influence of L1 on L2 and L2 on L1.
Use the plus sign with M when the magnetic fields of the two inductors are in phase, as shown in the figure below.

The minus sign is used with M when the magnetic fields of the two inductors oppose each other, as shown in the figure below.

Example problem: A 10-H coil is connected in series with a 5-H coil so the fields aid each other. Their mutual inductance is 7 H. What is the combined inductance of the coils?
Use the formula:
LT = L1 + L2 + 2M
LT = 10 H + 5 H + 2 (7 H)
LT = 29 H
THE ELECTROSTATIC FIELD
You previously learned that opposite electrical charges attract, while like electrical charges repel; this is because of the presence of an electrostatic field.
Any charged particle is surrounded by invisible lines of force, called electrostatic lines of force.
These lines of force have some interesting characteristics:
- They are polarized from positive to negative.
- They radiate from a charged particle in straight lines and do not form closed loops.
- They could pass through any known material.
- They could distort the orbits of tightly bound electrons.
Examine the figure to the right.
This figure represents two unlike charges surrounded by their electrostatic field.
Because an electrostatic field is polarized from positive to negative, arrows are shown radiating away from the positive charge and toward the negative charge.

Stated another way, the arrow field from the positive charge is pushing, while the field from the negative charge is pulling. The field attracts unlike charges.
In the figure below two like charges are shown with their surrounding electrostatic field.

If two unlike charges are placed on opposite sides of an atom whose outermost electrons cannot escape their orbits, the orbits of the electrons are distorted as shown.
Part (A) shows the normal orbit. Part (B) shows the same orbit in the presence of charged particles. Since the electron has a negative charge, the positive charge attracts it, pulling the electron toward it.
The negative charge repels electrons, pushing them farther away. This ability of an electrostatic field to attract and repel charges allows the capacitor to store energy.
THE SIMPLE CAPACITOR
A simple capacitor consists of two metal plates separated by an insulating material called a dielectric, as illustrated below.

Note that one plate is connected to the positive terminal of a battery; the other plate is connected to the negative terminal via a closed switch (S1).
Remember, an insulator is a material whose electrons cannot easily escape their orbits.
Due to the battery voltage, plate A is positively charged, and plate B is negatively charged. (How this happens is explained later in this lesson.)
Thus, an electrostatic field forms between the positive and negative plates.
The electrons on the negative plate (plate B) are attracted to the positive charges on the positive plate (plate A). Notice that the electrostatic field distorts the orbits of the electrons in the dielectric material.
The distortion occurs because the electrons in the dielectric are attracted to the top plate while being repelled from the bottom plate.
When switch S1 is opened, the battery is removed from the circuit, and the capacitor retains the charge. This occurs because the dielectric material is an insulator, and the electrons in the bottom plate (negative charge) have no path to reach the top plate (positive charge).
The distorted orbits of the atoms of the dielectric, plus the electrostatic force of attraction between the two plates, hold the positive and negative charges in their original position.
Thus, the energy stored in the battery is now distributed across the capacitor’s electrostatic field.
Two slightly different symbols for representing a capacitor are shown in the figure below.

Notice that each symbol is composed of two plates separated by a space that represents the dielectric.
The curved plate in (B) indicates that the plate should be connected to a negative polarity.
THE FARAD
Capacitance is measured in units called farads. Farad can be expressed by the formula:
![]()
The farad is a very large unit of measurement of capacitance.
For convenience, the microfarad (abbreviated µF) or the picofarad (abbreviated pF) or 1 × 10–6 farad, and 1.0 picofarad is equal to 0.000000000001 farad or 1.0 × 10–12 farad.
Capacitance is a physical property of the capacitor and does not depend on circuit characteristics such as voltage, current, or resistance.
A given capacitor always has the same value of capacitance (farads) in one circuit as in any other circuit in which it is connected.
FACTORS AFFECTING THE VALUE OF CAPACITANCE
The value of capacitance of a capacitor depends on three factors:
- The area of the plates.
- The distance between the plates.
- The dielectric constant of the material between the plates.
Plate area affects capacitance in the same way that container size affects the amount of water it can hold.
A capacitor with a large plate area can store more charge than a capacitor with a small plate area.
Stated, “The larger the plate area, the larger the capacitance.”
The second factor affecting capacitance is the distance between the plates. Electrostatic lines of force are strongest when the charged particles that create them are close together. When the charged particles are moved further apart, the lines of force weaken, and the ability to store a charge decreases.
The third factor affecting capacitance is the dielectric constant of the insulating material between the capacitor plates. The various insulating materials used as dielectrics in capacitors differ in their ability to respond to (pass) electrostatic lines of force.
A dielectric material, or insulator, is rated according to its ability to respond to electrostatic lines of force in terms of a figure called the dielectric constant.
A dielectric material with a high dielectric constant is a better insulator than a dielectric material with a low dielectric constant.
Dielectric constants for some common materials are given in the following list:
Material Constant
Vacuum 1.0000
Air 1.0006
Paraffin paper 3.5
Glass 5 to 10
Mica 3 to 6
Rubber 2.5 to 35
Wood 2.5 to 8
Glycerin (15ºC) 56
Petroleum 2
Pure water 81
Notice the dielectric constant for a vacuum. Since a vacuum is the standard of reference, it is assigned a constant of one.
The dielectric constants of all materials are compared to that of a vacuum.
Since the dielectric constant of air has been determined to be approximately the same as that of a vacuum, the dielectric constant of AIR is also considered to be equal to one.
The formula used to compute the value of capacitance is:
![]()
Where:
C = capacitance in picofarads
A = area of one plate, in square inches
d = distance between plates, in inches
K = dielectric constant of the insulating material
.2249 = a constant resulting from conversion from Metric to English units.
Example Problem: Find the capacitance of a parallel plate capacitor with paraffin paper as the dielectric.
Given:
K = 3.5
d = 0.05 inches
A = 12 square inches
Solution:
![]()
![]()
![]()
By examining the above formula, you can see that capacitance varies directly with the dielectric constant and the area of the capacitor plates, and inversely with the distance between the plates.
VOLTAGE RATINGS OF CAPACITORS
In selecting or substituting a capacitor for use, consideration must be given to
- The value of capacitance desired and
- The amount of voltage to be applied across the capacitor.
If the voltage applied across the capacitor is too great, the dielectric will break down, and arcing will occur between the capacitor plates.
When this happens, the capacitor becomes a short circuit, and direct current flowing through it can damage other electronic components. Each capacitor has a voltage rating (a working voltage) that should not be exceeded.
The working voltage of a capacitor is the maximum voltage that can be applied continuously without risking dielectric breakdown. The working voltage depends on the dielectric material used and its thickness. A high-voltage capacitor with a thick dielectric must have a relatively large plate area to achieve the same capacitance as a similar low-voltage capacitor with a thin dielectric.
The working voltage also depends on the applied frequency because losses and the resulting heating increase with frequency.
A capacitor with a voltage rating of 500 volts DC cannot be safely subjected to an alternating voltage or a pulsating direct voltage having an effective value of 500 volts.
Since an alternating voltage of 500 volts (RMS) has a peak value of 707 volts, a capacitor to which it is applied should have a working voltage of at least 750 volts.
In practice, select a capacitor whose working voltage is at least 50 percent greater than the highest effective voltage to be applied.
CAPACITOR LOSSES
Power loss in a capacitor may be attributed to dielectric hysteresis and dielectric leakage. Dielectric hysteresis may be defined as an effect in a dielectric material, like the hysteresis found in a magnetic material.
It results from rapid reversals in the polarity of the line voltage, which alter the orientation of electron orbits in the dielectric.
The amount of power loss due to dielectric hysteresis depends upon the type of dielectric used. A vacuum dielectric has the smallest power loss.
Dielectric leakage occurs in a capacitor when current flows through the dielectric. Normally, it is assumed that the dielectric effectively prevents current from flowing through the capacitor.
Although the dielectric’s resistance is extremely high, a small amount of current still flows. Ordinarily, this current is so small that for all practical purposes, it is ignored.
However, if leakage through the dielectric is abnormally high, the capacitor will rapidly discharge and overheat.
Capacitor power loss is determined by dielectric loss. If the loss is negligible and the capacitor returns the total charge to the circuit, it is a perfect capacitor with zero power loss.
CHARGING AND DISCHARGING A CAPACITOR
CHARGING
To better understand a capacitor’s behavior with other components, we first analyze the charge and discharge actions of a purely capacitive circuit.
For ease of explanation, the capacitor and voltage source shown in this figure are assumed to be ideal (no internal resistance), although this is not the practical case.
Figure (A) shows an uncharged capacitor connected to a four-position switch. With the switch in position 1, the circuit is open, and no voltage is applied to the capacitor.

With the switch in position 1, the circuit is open, and no voltage is applied to the capacitor.
Initially, each plate of the capacitor is a neutral body, and until a difference of potential is impressed across the capacitor, no electrostatic field can exist between the plates.
To charge the capacitor, the switch must be thrown to position 2, placing the capacitor across the battery terminals.
Under ideal conditions, the capacitor would reach full charge instantaneously.
However, charging occurs over time, allowing a step-by-step analysis.
At the instant the switch is thrown to position 2 (Figure B above), electrons are displaced simultaneously throughout the circuit.
This electron displacement is directed away from the negative terminal and toward the positive terminal of the source (the battery). A brief surge of current will flow as the capacitor charges.
If it were possible to analyze the motion of the individual electrons in this surge of charging current, the following action would be observed.
At the instant the switch is closed, the positive terminal of the battery extracts an electron from the bottom conductor.
The negative terminal of the battery forces an electron into the top conductor. At this same instant, an electron is forced into the top plate of the capacitor, and another is pulled from the bottom plate.
Thus, in every part of the circuit, a clockwise displacement of electrons occurs simultaneously.
As electrons accumulate on the top plate of the capacitor and others depart from the bottom plate, a potential difference develops across the capacitor.
Each electron forced onto the top plate makes that plate more negative, while each electron removed from the bottom plate makes it more positive.
Notice that the polarity of the voltage that builds up across the capacitor is such as to oppose the source voltage. The source voltage (EMF) forces current around the circuit clockwise.

The EMF developed across the capacitor, however, tends to drive the current counterclockwise, opposing the source EMF.
As the capacitor continues to charge, its voltage rises until it equals the source voltage. Once the capacitor voltage equals the source voltage, the two voltages balance, and the current stops flowing in the circuit.
In studying the charging process of a capacitor, you must be aware that no current flows through the capacitor. The material between the capacitor plates must be an insulator.
However, to an observer stationed at the source or along one of the circuit conductors, the action has all the appearances of a true flow of current, even though the insulating material between the plates of the capacitor prevents the current from having a complete path.
The current that appears to flow through a capacitor is called Displacement Current.

When a capacitor is fully charged and the source voltage equals the counter-electromotive force (CEMF) across the capacitor, the electrostatic field between the plates is maximum.
Since the electrostatic field is maximum, the energy stored in the dielectric is also maximum. If the switch is now opened, the electrons on the upper plate are isolated.
The electrons on the top plate are attracted to the charged bottom plate.
Because the dielectric is an insulator, the electrons cannot cross the dielectric to the bottom plate.
The electrostatic field will effectively trap the charges on both plates, keeping the capacitor charged indefinitely.
Note that the insulating dielectric material in a practical capacitor is not perfect, and a small leakage current will flow through the dielectric.
This current will eventually dissipate the charge. However, a high-quality capacitor may hold its charge for a month or more.
To summarize,
- When a capacitor is connected across a voltage source, a surge of charging current flows.
- This charging current develops a CEMF across the capacitor, which opposes the applied voltage.
- When the capacitor is fully charged, the CEMF equals the applied voltage, and the charging current ceases.
- At full charge, the electrostatic field between the plates is at maximum intensity, and the energy stored in the dielectric is maximum.
- If the charged capacitor is disconnected from the source, it will retain charge for some time.
- The length of time the charge is retained depends on the amount of leakage current present.
- Since a charged capacitor stores electrical energy, it can act as a source of EMF.
DISCHARGING
To discharge a capacitor, the charges on the two plates must be neutralized. This is accomplished by providing a conducting path between the two plates, as shown in the figure below.

With the switch in position (4), the excess electrons on the negative plate can flow to the positive plate, neutralizing its charge.
When the capacitor is discharged, the electrons’ distorted orbits in the dielectric return to their normal positions, and the stored energy is returned to the circuit.
A capacitor does not consume power. The energy the capacitor draws from the source is recovered when it discharges.
CHARGING AND DISCHARGING AN RC SERIES CIRCUIT
Ohm’s law states that the voltage across a resistor equals the current through it multiplied by the resistance; this means a voltage develops across a resistor only when current flows through it. A capacitor can store an electric charge.
When uncharged, both plates of the capacitor contain essentially the same number of free electrons. When charged, one plate contains more free electrons than the other plate.
The difference in the number of electrons measures the capacitor’s charge.
This charge builds up a voltage across the capacitor’s terminals, and the charge continues to increase until this voltage equals the applied voltage.
The charge in a capacitor is related to the capacitance and voltage as Q = CE, in which Q is the charge in coulombs, C is the capacitance in farads, and E is the EMF across the capacitor in volts.
CHARGE CYCLE
A voltage divider containing resistance and capacitance is connected in a circuit utilizing a switch, as shown at the top of the figure below. Such a series arrangement is called an RC series circuit.

In explaining the charge and discharge cycles of an RC series circuit, the time interval from time t0 (time zero, when the switch is first closed) to time t1 (time one, when the capacitor reaches full charge or discharge potential) will be used.
(Note that switches S1 and S2 move at the same time and can never both be closed at the same time.)
When switch S1 is closed at t0, the source voltage (ES) is applied across the entire circuit.
- Graph (A) shows an instantaneous rise at t0 from zero to the source voltage (Es = 6 V). Total voltage can be measured across the circuit between points 1 & 2.
- Graph (B) represents the charging current in the capacitor (id). At time t0, the charging current is at its MAXIMUM.
As time progresses toward t1, the current flowing into the capacitor decreases continuously.
The voltage buildup across the capacitor reduces the flow.
At time t1, the current flowing into the capacitor stops. At this point, the capacitor is fully charged and has stored its maximum energy in its electrostatic field.
- Graph (C) represents the voltage drop (e) across the resistor (R).
The value of er is determined by the amount of current flowing through the resistor on its way to the capacitor.
At time t0, the current flowing into the capacitor is at its maximum.
Thus, the voltage drop across the resistor is maximum (E = IR).
As time progresses toward t1, the current flowing to the capacitor steadily decreases, causing the voltage developed across the resistor (R) to decrease as well.
When t1 is reached, the current flowing to the capacitor stops, and the voltage across the resistor decreases to zero.
Remember that capacitance opposes a change in voltage. This is shown by comparing graphs (A) and (D).

In graph (A), the voltage across the circuit changed instantly from 0 to 6 volts, while the voltage developed across the capacitor in graph (D) required the entire time interval from t0 to t1 to reach 6 volts.
This is because at time t0, the maximum current flows through R, and the entire circuit voltage is dropped across the resistor. The voltage impressed across the capacitor at t0 is zero volts.
As time progresses toward t1, the decreasing current causes progressively less voltage to be dropped across the resistor (R), and more voltage builds up across the capacitor (C).
At time t1, the voltage felt across the capacitor is equal to the source voltage (6 volts), and the voltage dropped across the resistor (R) is equal to zero.
This is the complete charge cycle of the capacitor.
As you may have noticed, the processes that take place in the time interval t0 to t1 in a series RC circuit are exactly opposite to those in a series LR circuit.
For comparison, the key points of the charge cycles of RC and LR circuits are summarized in the table below.

DISCHARGE CYCLE
In the figure below, at time t0, the capacitor is fully charged.
When S1 is open and S2 closes, the capacitor discharge cycle starts.

At first, the circuit voltage attempts to go from the source potential (6 volts) to zero volts, as shown in graph (A). Remember, though, that the capacitor stores energy in an electrostatic field during the charge cycle.
Because S2 is closed at the same time S1 is open, the stored energy of the capacitor now has a path for current to flow.
At t0, the discharge current (id) from the bottom plate of the capacitor through the resistor (R) to the top plate of the capacitor (C) is maximum.
As time progresses toward t1, the discharge current steadily decreases until, at time t1, it reaches zero, as shown in graph (B)
The discharge causes a corresponding drop in voltage across the resistor, as shown in graph (C).
At time t0, the current through the resistor is maximum, and the voltage drop (er) across the resistor is maximum.
As the current through the resistor decreases, the voltage drop across it decreases until, at t1, it reaches zero.
Graph (D) shows the voltage across the capacitor (ec) during discharge.
At time t0, the voltage is at its maximum, and as time progresses toward t1, the energy stored in the capacitor is depleted.
At the same time, the voltage across the resistor decreases, and the voltage (e) across the capacitor decreases until, at time t1, the voltage (ec) reaches zero.
By comparing graph (A) with graph (D), you can see the effect that capacitance has on a change in voltage.

If the circuit had not contained a capacitor, the voltage would have dropped to zero at the instant S1 was opened at time t0.
Because the capacitor is in the circuit, a voltage is applied until it is completely discharged at t1.
Capacitance opposes this change in voltage.
RC TIME CONSTANT
The time required to charge a capacitor to 63 percent (63.2 percent) of its full charge or to discharge it to 37 percent (36.8 percent) of its initial voltage is known as the Time Constant (TC) of the circuit.
The charge and discharge curves of a capacitor are shown below.
Note that the charge curve is like the curve in graph (D) from the Charge Cycle section above, and the Discharge Curve is like the curve from graph (B).
The value of the time constant in seconds is equal to the product of the circuit resistance in ohms and the circuit capacitance in farads.
The value of the one-time constant is expressed mathematically as t = RC.
Some forms of this formula used in calculating RC time constants are:
t (in seconds) = R (in ohms) x C (in farads)
UNIVERSAL TIME CONSTANT CHART
Because the impressed voltage and the values of R and C or R and L in a circuit are usually known, the Universal Time Constant Chart (figure below) can be used to find the time constant of the circuit.

Curve A is a plot of both the capacitor voltage during charge and the inductor current during growth.
Curve B is a plot of both the capacitor voltage during discharge and the inductor current during decay.
The time scale (horizontal scale) is graduated in terms of the RC or LR time constants, so that the curves may be used for any values of R and C, or L and R.
The voltage and current scales (vertical scales) are graduated as percentages of the maximum voltage or current, so that the curves may be used for any value of voltage or current.
If the time constant and the initial or final voltage for the circuit in question are known, the voltages across the various parts of the circuit can be obtained from the curves for any time after the switch is closed, either on charge or discharge. The same reasoning applies to the circuit’s current.
CAPACITORS IN SERIES AND PARALLEL
Capacitors may be connected in series or in parallel to obtain a resultant value which may be either the sum of the individual values (in parallel) or a value less than that of the smallest capacitance (in series).
CAPACITORS IN SERIES
Connecting capacitors in series moves their plates farther apart. This is shown in the figure below.

Notice that the junction between C1 and C2 has both a negative and a positive charge. This makes the junction essentially neutral.
The total capacitance of the circuit is developed between the left plate of C1 and the right plate of C2. Because these plates are farther apart, the circuit’s total capacitance decreases.
Solving for the total capacitance (CT) of capacitors connected in series is like solving for the total resistance (RT) of resistors connected in parallel.
Note the similarity between the formulas for RT and CT:
![]()
![]()
If the circuit contains more than two capacitors, use the above formula. If the circuit contains only two capacitors, use the formula below:
![]()
Note: All values for CT, C1, C2, C3… Cn should be in farads.
It should be evident from the above formulas that the total capacitance of capacitors in series is less than the capacitance of any of the individual capacitors.
Example Problem:
Given:
![]()
![]()
![]()
Step by step equations
![]()
![]()
![]()
![]()
![]()
![]()
The total capacitance of 0.008 μF is slightly smaller than the smallest capacitor (0.01 μF).
CAPACITORS IN PARALELL
When capacitors are connected in parallel, one plate of each capacitor is connected directly to one terminal of the source. In contrast, the other plate of each capacitor is connected to the other terminal of the source.
The figure below shows all the negative plates of the connected capacitors and all the positive plates connected together.

CT, therefore, appears as a capacitor with a plate area equal to the sum of all the individual plate areas.
As previously mentioned, capacitance is directly proportional to plate area. Connecting capacitors in parallel effectively increases plate area and thereby increases total capacitance.
For capacitors connected in parallel, the total capacitance is the sum of all the individual capacitances. The total capacitance of the circuit may be calculated using the formula:
CT = C1 + C2 + C3 + … + CN,
where all capacitances are in the same units.
Example Problem: Determine the total capacitance in a parallel capacitive circuit containing three capacitors whose values are 0.03 μF, 2.0 μF, and 0.25 μF, respectively.
Given:
C1 = 0.03 µF
C2 = 2 µF
C3 = 0.25 µF
Solution:
CT = C1 + C2 + C3
CT = 0.03 µF + 2.0 µF + 0.25 µF
CT = 2.28 µF
TYPES OF CAPACITORS
Capacitors are manufactured in various forms and may be divided into two main classes: fixed capacitors and variable capacitors.
A fixed capacitor has a constant capacitance. A variable capacitor allows the capacitance to be varied or adjusted, which is beyond the scope of this topic. As an electrician, you work with fixed-frequency AC power (60 Hz in the US). When you use capacitors—like a motor start capacitor or a power factor correction bank—you need a specific, constant capacitance value to handle a specific load.
ELECTROLYTIC CAPACITOR

An electrolytic capacitor can be used when a large capacitance is required.
As the name implies, an electrolytic capacitor contains an electrolyte.
A dry electrolytic capacitor consists essentially of two metal plates separated by the electrolyte.
In most cases, the capacitor is housed in a cylindrical aluminum container that serves as the negative terminal.
The positive terminal (or terminals, if the capacitor is multi-section) is a lug (or lugs) at the bottom end of the container.
The capacitance value(s) and the voltage rating of the capacitor are generally printed on the side of the aluminum case.
The large capacitance of electrolytic capacitors makes them particularly suitable for passing or bypassing low-frequency signals and storing large amounts of energy.
They are widely used in power supplies and for decoupling unwanted AC components from DC power connections.
Electrolytic capacitors range downwards from tens (exceptionally hundreds) of thousands of microfarads to about 100 nanofarads—smaller sizes are possible but have no advantage over other types.
Electrolytic capacitors are available with working voltages up to about 500V, although the highest capacitance values are not available at high voltage. The working temperature is typically 85°C for standard use and 105 °C for high-temperature use; higher-temperature units are available but uncommon.
Unlike other types of capacitors, most electrolytic capacitors require that the voltage applied to one terminal (the anode) never become negative relative to the other (they are said to be “polarized”), so they cannot be used with AC signals without a DC polarizing bias (non-polarized electrolytic capacitors are available for special purposes).
Capacitors can lose capacitance as they age and lose electrolytes, particularly at high temperatures. A common failure mode that causes difficult-to-find circuit malfunctions is a progressively increasing ESR without a change in capacitance, again, particularly at high temperatures.
The dielectric type and thickness determine the maximum voltage that can be safely applied to the electrolytic capacitor. If the applied voltage is high enough to ionize the atoms of the dielectric material, arcing between the plates will occur.
In most other types of capacitors, arcing will destroy the capacitor. However, an electrolytic capacitor can be self-healing. If the arcing is small, the electrolyte will regenerate itself. If the arcing is too large, the capacitor will not self-heal and will become defective.
FILM CAPACITOR

Film capacitors are made out of two pieces of plastic film covered with metallic electrodes, wound into a cylindrical shape, with terminals attached, and then encapsulated. In general, film capacitors are not polarized, so the two terminals are interchangeable. There are two different types of plastic film capacitors, made with two different electrode configurations:
- Film/foil capacitors, or metal foil capacitors, use two plastic films as the dielectric. Each is layered with a thin metal foil, usually aluminum, as the electrodes. Advantages of this construction type include easy electrical connection to the metal-foil electrodes and its ability to withstand high-current surges.
- Metalized film capacitors consist of two metalized films separated by a plastic dielectric. A very thin (~ 0.03 μm) vacuum-deposited aluminum metallization is applied to one or both sides to serve as electrodes. This configuration can have “self-healing” properties, in that dielectric breakdowns orshort circuits between the electrodes do not necessarily destroy the component. With this basic design, it is possible to make high-quality products such as “zero defect” capacitors and to produce wound capacitors with higher capacitance values (up to 100 μF and higher) in smaller cases (higher volumetric efficiency) compared to film/foil construction. However, a disadvantage of the metalized construction is its limited current-surge rating.
A key advantage of the internal construction of every film capacitor is direct contact with the electrodes at both ends of the winding. This contact keeps all current paths very short.
The design behaves like multiple individual capacitors connected in parallel, thereby reducing internal ohmic losses (ESR) and parasitic inductance (ESL).
The inherent geometry of the film capacitor structure results in low ohmic losses and a low parasitic inductance, making them suitable for applications with high surge currents (snubbers), AC power applications, and higher frequencies.
Another feature of film capacitors is the ability to choose different film materials for the dielectric layer to achieve desirable electrical characteristics, such as stability, a wide temperature range, or the ability to withstand very high voltages. Polypropylene film capacitors are specified for their low electrical losses and nearly linear behavior over a very wide frequency range, making them suitable for stability Class 1 applications in resonant circuits, comparable only to ceramic capacitors. The film/foil variants of plastic film capacitors are especially capable of handling high- and very-high-current surges.
The unique mechanical properties of plastic and paper films, when configured appropriately, enable their use in very large-capacity capacitors. The larger film capacitors are used as power capacitors in electrical power installations and plants, capable of withstanding very high power or very high applied voltages. The dielectric strength of these capacitors can reach into the four-digit voltage range.
Inductive and Capacitive Reactance
You have already learned how inductance and capacitance individually behave in a direct current circuit. In this lesson, you will be shown how inductance, capacitance, and resistance affect alternating current.
Inductance and Alternating Current
This might be a good place to recall what you learned about the phase.
When two things are in step, going through a cycle together, falling together, and rising together, they are in phase.
When they are out of phase, the angle of lead or lag, the number of electrical degrees by which one of the values leads or lags the other, is a measure of the amount they are out of step.
The time it takes the current in an inductor to build up to maximum and to fall to zero is important for another reason.
It illustrates a very useful characteristic of inductive circuits: the current through the inductor always lags behind the voltage across it.
A circuit with pure resistance (if such a thing were possible) would have the alternating current through it and the voltage across it rise and fall together. Figure (A) illustrates this, showing the sine-wave current and voltage in a purely resistive circuit driven by an AC source.

The current and voltage do not have the same amplitude, but they are in phase.
In the case of a circuit with inductance, the opposing force of the counteremf would be enough to keep the current from remaining in phase with the applied voltage.
You learned that in a DC circuit containing pure inductance, the current took time to rise to maximum even though the full applied voltage was immediately at maximum.
Figure (B) shows the waveforms for a purely inductive AC circuit in steps of quarter-cycles.

With an AC voltage, in the first quarter-cycle (0º to 90º), the applied voltage increases continuously.
If there were no inductance in the circuit, the current would also increase during the first quarter of the cycle. You know this circuit has inductance. Since inductance opposes any change in current flow, no current flows during the first quarter cycle.
In the next quarter-cycle (90º to 180º), the voltage decreases back to zero; current begins to flow in the circuit and reaches a maximum value at the same instant the voltage reaches zero. The applied voltage then builds up to its maximum in the other direction, followed by the resulting current.
When the voltage again reaches its maximum at the end of the third quarter-cycle (270º), all values are exactly opposite to what they were during the first half-cycle. The applied voltage leads the resulting current by one quarter-cycle or 90 degrees.
To complete the full 360º cycle, the voltage decreases to zero again, and the current reaches its maximum value.
You must not get the idea that any of these values stop cold at a particular instant. Until the applied voltage is removed, both current and voltage change in amplitude and direction.
As you know, the sine wave can be compared to a circle.

Just as you mark off a circle into 360 degrees, you can mark off the time of one cycle of a sine wave into 360 electrical degrees.
This relationship is shown in the figure to the right. By referring to this figure, you can see why the current is said to lag the voltage, in a purely inductive circuit, by 90 degrees. Furthermore, by referring to the figures to the right, you can see why the current and voltage are said to be in phase in a purely resistive circuit.
In a circuit having both resistance and inductance, then, as you would expect, the current lags the voltage by an amount somewhere between 0 and 90 degrees.
A simple memory aid to help you remember the relationship between voltage and current in an inductive circuit is the word ELI.
Since:
E is the symbol for voltage,
L is the symbol for inductance, and
I is the symbol for current.
The word ELI demonstrates that current comes after (Lags) voltage in an inductor.
INDUCTIVE REACTANCE
The reduction in current flow in a circuit due to inductive reactance is called inductive reactance.

By examining a coil of wire and applying Lenz’s law, we can see that inductance opposes changes in current in a circuit.
When the current flowing through an inductor continuously reverses itself, as in the case of an AC source, the inertia effect of the CEMF is greater than with DC.
The greater the amount of inductance (L), the greater the opposition from this inertia effect. Also, the faster the current reverses, the greater this inertial opposition. This opposing force that an inductor presents to the flow of alternating current cannot be called resistance, since it is not the result of friction within a conductor.
The name given to it is inductive reactance because it is the “reaction” of the inductor to the changing value of alternating current. Inductive reactance is measured in ohms, and its symbol is XL.
As you know, the induced voltage in a conductor is proportional to the rate at which magnetic lines of force cut the conductor. The greater the rate (the higher the frequency), the greater the CEMF.
Also, the induced voltage increases with inductance; the more ampere-turns, the greater the CEMF. Reactance, then, increases with an increase in frequency and with an increase in inductance.
The formula for inductive reactance is as follows:
XL = 2πfL
Where
XL is inductive reactance in ohms
2π is 6.28 (2 X 3.1416)
f is the frequency of the alternating current in hertz
L is the inductance in henrys
Example problem: illustrates how to compute XL.
Given:
f = 60 Hz
L = 20 H
Solution:
XL = 2πfL
XL = 6.28 x 60 Hz x 20 H
XL = 7.536Ω
CAPACITORS AND ALTERNATING CURRENT
The four parts of the figure below show the variation of the alternating voltage and current in a capacitive circuit, for each quarter of one cycle.
- The solid line represents the capacitor voltage, and the dotted line represents the capacitor current.

- The line running through the center is the zero, or reference point, for both the voltage and the current.
- The bottom line indicates the cycle time in electrical degrees.
Assume that the AC voltage has been acting on the capacitor for some time before the time represented by the starting point of the sine wave in the figure.
At the beginning of the first quarter-cycle (0º to 90º), the voltage has just passed through zero and is increasing in the positive direction.
Since the zero point is the steepest part of the sine wave, the voltage is changing at its greatest rate. The charge on a capacitor varies directly with the voltage across it. Therefore, the capacitor’s charge is changing at its greatest rate at the beginning of the first quarter-cycle.
In other words, the greatest number of electrons is moving off one plate and onto the other plate.
Thus, the capacitor current is at its maximum value, as shown in part (A) of the figure.
As the voltage approaches its maximum at 90 degrees, its rate of change decreases, so the current must decrease toward zero.
At 90 degrees, the voltage across the capacitor is maximum, the capacitor is fully charged, and there is no further movement of electrons from plate to plate. That is why the current at 90 degrees is zero.
At the end of this first quarter cycle, the alternating voltage stops increasing in the positive direction and starts decreasing. It is still a positive voltage, but to the capacitor, the decrease in voltage means the plate, which has just accumulated an excess of electrons, must lose some of them.
The current flow, therefore, must reverse its direction.
Part (B) of the figure shows that the current curve lies below the zero line (negative current direction) during the second quarter cycle (90° to 180°).
At 180 degrees, the voltage has dropped to zero. This means that, for a brief instant, the electrons are equally distributed between the two plates; the current is at its maximum because the rate of change of voltage is at its maximum.
Just after 180 degrees, the voltage reverses polarity and begins to build to its maximum negative peak, which is reached at the end of the third quarter-cycle (180º to 270º).
During this third-quarter cycle, the rate of voltage change gradually decreases as the charge builds up to a maximum of 270 degrees.
At this point, the capacitor is fully charged, and it carries the full impressed voltage.
Because the capacitor is fully charged, no further electrons are exchanged; therefore, the current is zero. The conditions are exactly the same as at the end of the first quarter cycle (90º), but the polarity is reversed.
Just after 270 degrees, the impressed voltage again decreases, and the capacitor must lose electrons from the negative plate.
It must discharge, starting at a minimum flow rate and rising to a maximum.
This discharging action continues through the last quarter cycle (270º to 360º) until the impressed voltage has reached zero.
At 360 degrees, you are back at the beginning of the cycle, and everything starts over.
If you examine the complete voltage and current curves in part D, you will see that the current always lags the voltage by 90 degrees due to charging and discharging.
You know that the time and voltage relationship is called the phase relationship.
The voltage-current phase relationship in a capacitive circuit is exactly the opposite of that in an inductive circuit. The current in a capacitor leads the voltage across it by 90 degrees.
You realize that the current and voltage are both undergoing their own cycles simultaneously while the AC voltage is applied.
The current does not go through part of its cycle (charging or discharging), stop, and wait for the voltage to catch up. The voltage amplitude and polarity, and the current amplitude and direction, continually change.
Their positions relative to each other and to the zero line at any electrical instant, between 0 and 360 degrees, can be seen by reading upward from the time-degree line.
The current swing from the positive peak at zero degrees to the negative peak at 180 degrees is NOT a measure of the number of electrons or the charge on the plates.
It shows the direction and strength of the current relative to the polarity and magnitude of the voltage appearing across the plates.
At times, it is convenient to use the word “ICE” to remember the phase relationship of the current and voltage in capacitive circuits.
Since
I is for current.
C is for capacitor
E is for voltage
This memory aid is like the “ELI” term used to remember the relationship between current and voltage in an inductor.
The phrase “ELI the ICE man” helps remember the phase relationship between the inductor and the capacitor.
Since the capacitor plates change polarity at the same rate as the AC voltage, the capacitor appears to pass an alternating current.
The electrons do not pass through the dielectric, but their back-and-forth motion between plates causes a current to flow in the circuit.
It is convenient, however, to say that the alternating current flows “through” the capacitor.
You know this is not true, but the expression avoids a lot of trouble when speaking of current flow in a circuit containing a capacitor.
By the same shortcut, you may say that the capacitor does not pass a direct current (if both plates are connected to a DC source, the current will flow only long enough to charge the capacitor).
With a capacitor-type hookup in a circuit containing both AC and DC, only the AC will be “passed” on to another circuit.
You have now learned two things to remember about a capacitor:
- A capacitor will appear to conduct an alternating current and
- A capacitor will not conduct a direct current.
CAPACITIVE REACTANCE
So far, you have been treating the capacitor as a device that passes AC, with the only opposition to the alternating current being the normal circuit resistance present in any conductor.
However, capacitors themselves offer very real opposition to current flow.
This opposition arises because, at a given voltage and frequency, the number of electrons that go back and forth between the plates is limited by the capacitor’s storage capacity.
As the capacitance increases, a greater number of electrons change plates each cycle, and (since current is the rate of electrons passing a given point) the current increases.
Increasing the frequency will also decrease the opposition offered by a capacitor.
This occurs because the number of electrons the capacitor can hold at a given voltage determines how often the plates change.
As a result, more electrons will pass a given point in a given time (higher current).
The opposition that a capacitor offers to AC is therefore inversely proportional to frequency and capacitance.
This opposition is called Capacitive Reactance.
You may say that capacitive reactance decreases with increasing frequency or, for a given frequency, the capacitive reactance decreases with increasing capacitance.
The symbol for capacitive reactance is XC.
Now you can understand why XC varies inversely with the product of the frequency and capacitance.
Where:
XC is capacitive reactance in ohms
f is the frequency in hertz
C is capacitance in farads
2π is 6.28 (2 X 3.1416)
Example problem: illustrates how to compute XC.
Given:
f = 100 Hz
C = 50 µF
Formula:
![]()
Solution:
![]()
![]()
![]()
REACTANCE, IMPEDANCE, AND POWER RELATIONSHIPS IN AC CIRCUITS
Up to this point, we have explained inductance and capacitance individually in AC circuits.
The rest of this lesson will concern the combination of inductance, capacitance, and resistance in AC circuits.
To explain the various properties of AC circuits, we will use the series RLC circuit.

The symbol marked E in the figure is the general symbol for an AC voltage source.
REACTANCE
Inductive reactance causes the current to lag the voltage, while capacitive reactance causes the current to lead the voltage.
Therefore, since inductive reactance and capacitive reactance are exactly opposite in their effects, what will be the result when the two are combined?
It is not hard to see that the net effect is a tendency to cancel each other, with the combined effect then equal to the difference between their values.
This resultant is called reactance; it is represented by the symbol X and expressed by the equation:
X = XL – XC or X = XC – XL.
Thus, if a circuit contains 50 ohms of inductive reactance and 25 ohms of capacitive reactance in series, the net reactance, or X, is 50 ohms – 25 ohms, or 25 ohms of inductive reactance.
Example problem: Suppose you have a circuit containing an inductor of 100 μH in series with a capacitor of 0.001 μF, operating at a frequency of 4 MHz.
What is the value of net reactance, or X?
Given:
f = 4 MHz
L = 100 µH
C = .001 µF
2π = 6.28 (2 X 3.1416)
Solution:
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Now assume you have a circuit containing a 100-μH inductor in series with a 0.0002-μF capacitor, operating at 1 MHz.
What is the value of the resultant reactance in this case?
Given:
f = 1MHz
L = 100 µH
C = .0002 µF
2π = 6.28 (2 X 3.1416)
Solution:
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
You will notice that in this case, the inductive reactance is smaller than the capacitive reactance and is therefore subtracted from the capacitive reactance.
These two examples serve to illustrate an important point: when capacitive and inductive reactances are combined in series, the smaller is subtracted from the larger, and the resultant reactance takes on the characteristics of the larger.
IMPEDANCE
From your study of inductance and capacitance, you know how inductive reactance and capacitive reactance act to oppose the flow of current in an AC circuit. However, another factor, the resistance, also opposes the flow of current.
Since, in practice, AC circuits with reactance also contain resistance, the two oppose each other, reducing the current. This combined opposition by resistance and reactance is called impedance and is represented by the symbol Z.
Since the values of resistance and reactance are both given in ohms, it might at first seem possible to determine the value of the impedance by simply adding them together. However, you cannot do it that easily. You know that in an AC circuit that contains only resistance, the current and the voltage will be in step (that is, in phase) and will reach their maximum values at the same instant.
You also know that in an AC circuit containing only reactance, the current will either lead or lag the voltage by one-quarter of a cycle or 90 degrees. Therefore, the voltage in a purely reactive circuit will differ in phase by 90 degrees from that in a purely resistive circuit, and for this reason, reactance and resistance are not combined by simply adding them.
When reactance and resistance are combined, the impedance will be greater than either alone.
The current will also not be in step with the voltage, nor will it differ in phase by exactly 90 degrees; rather, it will be somewhere between the in-step and 90-degree out-of-step conditions. The greater the reactance relative to the resistance, the more nearly the phase difference will approach 90º.
The larger the resistance compared to the reactance, the more the phase difference will approach zero degrees. If the value of resistance and reactance cannot simply be added together to find the impedance or Z, how is it determined?
Because the current through a resistor is in phase with the voltage across it, and the current in a reactance lags the voltage across it by 90 degrees, the two are orthogonal. They can therefore be combined using the same method used to construct a right-angle triangle.
Assume you want to find the impedance of a series combination of 8 ohms of resistance and 5 ohms of inductive reactance.
Start by drawing a horizontal line, R, representing 8 ohms of resistance, as the base of the triangle. Then, since the effect of the reactance is always at right angles, or 90 degrees, to that of the resistance, draw the line XL, representing 5 ohms of inductive reactance, as the altitude of the triangle.

This is shown in the figure to the right. Now, complete the hypotenuse (longest side) of the triangle. The hypotenuse represents the circuit’s impedance.
One of the properties of a right triangle is:
![]()
Applied to impedance thus becomes: (impedance)2 = (resistance)2 + (reactance)2
or
Given:
![]()
To Solve for Z:
When you have a capacitive reactance to deal with instead of an inductive reactance, as in the previous example, it is customary to draw the line representing the capacitive reactance in a downward direction.
In the figure shown below, the line for capacitive reactance is drawn downward to indicate that it acts in a direction opposite to inductive reactance, which is drawn upward.

In a series circuit containing capacitive reactance, the equation for finding the impedance becomes:
![]()
In many series circuits, you will find resistance combined with both inductive reactance and capacitive reactance.
Since you know that the value of the reactance, X, is equal to the difference between the values of the inductive reactance, XL, and the capacitive reactance, XC, the equation for the impedance in a series circuit containing R, XL, and XC then becomes:
![]()
NOTE: The formulas on this page can be used to calculate Z only if the resistance and reactance are connected in series.
In the figure below, you will see the method for determining the impedance of a series circuit comprising resistance, inductance, and capacitance.

Assume that 10 ohms of inductive reactance and 20 ohms of capacitive reactance are connected in series with 40 ohms of resistance.
Let the horizontal line represent the resistance R. The line drawn upward from the end of R represents the inductive reactance, XL.
Represent the capacitive reactance by a line drawn downward at right angles from the same end of R. Find the result of XL and XC by subtracting XL from XC. This resultant represents the value of X.
Thus:
The line Z will then represent the result of R and X. The value of Z can be calculated as follows:
Given:
XL = 10Ω
XC = 20Ω
R = 40Ω
Solution:
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
OHM’S LAW FOR AC
In general, Ohm’s law cannot be applied to alternating-current circuits since it does not consider the reactance that is always present in such circuits.
However, by modifying Ohm’s law to take into account the effect of reactance, we obtain a general law that applies to AC circuits.
Because the impedance, Z, represents the combined opposition of all the reactances and resistances, the general law for AC is:
![]()
This general modification applies to alternating current flowing in any circuit, and any one of the values may be found from the equation if the others are known.
Example problem: Suppose a series circuit contains an inductor having 5 ohms of resistance and 25 ohms of inductive reactance in series with a capacitor having 15 ohms of capacitive reactance.
If the voltage is 50 volts, what is the current?
Given:
R = 5
XL = 25 W
XC = 15 W
E = 50 V
Solution:
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Example Problem: Now, suppose the circuit contains an inductor with 5 ohms of resistance and 15 ohms of inductive reactance in series, and a capacitor with 10 ohms of capacitive reactance. If the current is 5 amperes, what is the voltage?
Given:
R = 5 W
XL = 15 W
XC = 10 W
I = 5A
Solution:
Power in AC Circuits
You know that in a direct current circuit, the power is equal to the voltage times the current, or P = E × I. If a 100-volt voltage is applied to a circuit that produces a current of 10 amperes, the power is 1000 watts. This is also true in an AC circuit when the current and voltage are in phase, i.e., when the circuit is effectively resistive. But if the AC circuit contains reactance, the current will lead or lag the voltage by a certain amount (the phase angle).
When the current is out of phase with the voltage, the product of the applied voltage and the total current indicates only the apparent power.
True power depends on the phase angle between the current and voltage. The symbol for phase angle is Θ (Theta). When an alternating voltage is impressed across a capacitor, power is drawn from the source and stored in the capacitor as the voltage increases from zero to its maximum. Then, as the impressed voltage decreases from its maximum value to zero, the capacitor discharges and returns the power to the source.
Likewise, as the current through the inductor increases from its zero value to its maximum value, the field around the inductor builds up to a maximum. When the current decreases from maximum to zero, the field collapses and returns the power to the source.
You can see, therefore, that no power is used up in either case since the power alternately flows to and from the source. The power returned to the source by the reactive components in the circuit is called reactive power.
In a purely resistive circuit, all the power is consumed, and none is returned to the source; in a purely reactive circuit, no power is consumed, and all the power is returned to the source. It follows that in a circuit that contains both resistance and reactance, there must be some power dissipated in the resistance as well as some returned to the source by the reactance.
In the figure below, you can see the relationship between the voltage, the current, and the power in such a circuit.

The part of the power curve shown below the horizontal reference line is the result of multiplying a positive instantaneous value of current by a negative instantaneous value of the voltage, or vice versa.
As you know, the product obtained by multiplying a positive value by a negative value will be negative.
Therefore, the power at that instant must be considered as negative power. In other words, during this time, the reactance was returning power to the source.
The instantaneous power in the circuit equals the product of the applied voltage and the current through the circuit.
When the voltage and current are of the same polarity, they act together and draw power from the source.
When polarities are opposed, power is returned to the source.
Briefly then, in an AC circuit that contains reactance and resistance, the apparent power is reduced by the power returned to the source, so that in such a circuit, the net power, or true power, is always less than the apparent power.
As mentioned earlier, the true power of a circuit is the power it uses. This power, measured in watts, is the power associated with the circuit’s total resistance.
CALCULATING TRUE POWER
Where:
True Power = (IR)2R
True Power is measured in watts.
IR is resistive current in amperes.
R is resistance in ohms.
Example Problem: Find the true power of the circuit shown in the figure below.
Given:
R = 60W
XL = 30W
XC = 110W
E = 500 V
Solution:
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Since the current in a series circuit is the same in all parts of the circuit:
True Power = (IR)2R
True Power = (5A)2 x 60Ω
True Power = 1500 watts
Calculating Reactive Power in AC Circuits
Reactive power is the power returned to the source by the circuit’s reactive components.
This type of power is measured in Volt-Amperes-Reactive, abbreviated VAR. Reactive power is calculated from the voltage and current associated with the circuit’s reactance.
Since the voltage of the reactance is equal to the reactance multiplied by the reactive current, reactive power can be calculated by the formula:
Reactive Power = (IX)2X
Where: Reactive power is measured in volt-amperes-reactive.
IX is a reactive current in amperes.
X is the total reactance in ohms.
Another way to calculate reactive power is to compute the inductive and capacitive powers and subtract the smaller from the larger.
Reactive Power = (IL)2XL – (IC)2XC Or = (IC)2XC – (IL)2XL
Where: Reactive power is measured in volt-amperes.
IC is capacitive current in amperes.
XC is capacitive reactance in ohms.
IL is an inductive current in amperes.
XL is inductive reactance in ohms.
Either formula will work. The formula you use depends on the values you are given in a circuit.
Example Problem: Find the reactive power of the circuit shown in the last example problem above.
Given:
XL = 30Ω
XC = 110Ω
X = 80Ω
I = 5A
Since this is a series circuit, the current (I) is the same throughout the circuit.
Solution:
Reactive power = (IX)2X
Reactive power = (5A)2 x 80Ω
Reactive power = 2,000 var
To prove the second formula also works
Reactive power = (Ic)2Xc – (IL)2XL
Reactive power = (5A)2 x 110Ω – (5A)2 x 30Ω
Reactive power = 2,750 var – 750 var
Reactive power = 2,000 var
Calculating Apparent Power in AC Circuits.
Apparent power is the power that appears to the source because of the circuit impedance.
Since the impedance is the total opposition to AC, the apparent power is the power the voltage source “sees.” Apparent power is the combination of true power and reactive power.
Apparent power is not found by simply adding true power and reactive power, any more than impedance is found by adding resistance and reactance.
To calculate apparent power, you may use either of the following formulas:
Apparent power = (Iz)2Z
Where Apparent power is measured in VA (volt-amperes)
IZ is the impedance current in amperes.
Z is the impedance in ohms
Or
![]()
Example problem: Find the apparent power for the circuit shown above.
Given
Z = 100Ω
I = 5A
Recall that the current in a series circuit is the same in all parts of the circuit.
Solution
Apparent power = (Iz)2Z
Apparent power = (5A)2 x 100Ω
Apparent power = 2,500 VA
Or Given
![]()
![]()
![]()
![]()
![]()
![]()
Power Factor
The power factor is a number (represented as a decimal or a percentage) that represents the portion of the apparent power dissipated in a circuit.
If you are familiar with trigonometry, the easiest way to find the power factor is to find the cosine of the phase angle (Θ).
The cosine of the phase angle equals the power factor. You do not need to use trigonometry to find the power factor.
Since the power dissipated in a circuit is true power, then:
Apparent Power X PF = True Power
Therefore,
![]()
If true power and apparent power are known, you can use the formula shown above. Going one step further, you can develop another formula for power factor. By substituting the equations for
true power and apparent power in the formula for power factor, you get:
![]()
Since the current in a series circuit is the same in all parts of the circuit, IR equals IZ. Therefore, in a series circuit.
![]()
Example Problem: To compute the power factor for the series circuit shown previously, you may use any of the above methods.
Given:
True Power = 1500W
Apparent Power = 2500 VA
Solution:
![]()
![]()
![]()
Another method:
Given:
![]()
![]()
![]()
Solution:
![]()
![]()
Note: As stated earlier, the power factor can be expressed as a decimal or percentage. In this example, the decimal number .6 could also be expressed as 60%.
Power Factor Correction
The apparent power in an AC circuit is the power the source “sees.” From the source’s perspective, apparent power is the power it must provide to the circuit. True power is the power actually used in the circuit.
The difference between apparent power and true power is wasted because, in reality, only true power is consumed. Ideally, apparent power and true power would be equal.
If this were the case, the power factor would be 1 (unity, 100%).
This condition can exist in two ways.
- If the circuit is purely resistive or
- If the circuit “appears” purely resistive to the source.
To make the circuit appear purely resistive, there must be no reactance. To have no reactance in the circuit, the inductive reactance (XL) and capacitive reactance (XC) must be equal.

Remember:
X = XL – XC
Therefore, when XL = XC, X = 0; the expression “correcting the power factor” refers to reducing the reactance in a circuit. The ideal situation is to have no reactance in the circuit.
This is accomplished by adding capacitive reactance to an inductive circuit and inductive reactance to a capacitive circuit.
For example, the circuit shown in the figure above has a net capacitive reactance of 80 ohms and a power factor of 0.6 (60%).
If 80 ohms of inductive reactance were added to this circuit (by adding another inductor), the circuit would have a total reactance of zero ohms and a power factor of 1 or 100 percent.
The apparent and true power of this circuit would then be equal.
Series RLC Circuits
The principles and formulas that have been presented in this lesson are used in all AC circuits.
The examples given have been series circuits.
This lesson section will not present any new material but will serve as an example of applying the principles presented so far.
Follow each example problem step by step to see how each formula depends on the information determined in earlier steps.

Example Problem: The example series RLC circuit shown in the figure above will be used to solve for XL, XC, X, Z, IT, true power, reactive power, apparent power, and power factor, round the values obtained to the nearest whole number.
First, solve for XL and XC.
Given:
F = 60 Hz
L = 27 mH
C = 380 µF
2π = 6.28 (2 X 3.1416)
Solution:
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Now solve for X
Given:
XC = 7Ω
XL = 10Ω
Solution:
X = XL – XC
X = 10W – 7Ω
X = 3W (Inductive)
Use the value of X to solve for Z
Given:
X = 3Ω
R = 4Ω
Solution:
![]()
![]()
![]()
![]()
![]()
The value of Z can be used to solve for the total current (IT)
Given:
Z = 5Ω
E = 110V
Solution:
![]()
![]()
![]()
Since the current is the same throughout a series circuit, IT can be used to determine the various power values.
Given:
IT = 22A
R = 4Ω
X = 3Ω
Z = 5Ω
Solution:
True Power = (IR)2R
True Power = (22A)2 x 4Ω
True Power = 1936 W
Reactive power = (IX)2X
Reactive power = (22A)2 x 3Ω
Reactive power = 1452 var
Apparent power = (Iz)2Z
Apparent power = (22A)2 x 5Ω
Apparent power = 2,420 VA
The power factor can now be found using either apparent power and true power or resistance and impedance. The math is easier if you use impedance and resistance.
Given:
R = 4Ω
Z = 5Ω
Solution:
![]()
![]()
![]()
PARALLEL RLC CIRCUITS
When dealing with a parallel AC circuit, you will find that the concepts presented in this lesson for series AC circuits still apply.
One major difference between a series circuit and a parallel circuit is important to consider.
The difference is that current is the same in all parts of a series circuit, whereas voltage is the same across all branches of a parallel circuit.
Because of this difference, you must compute the total impedance of a parallel circuit based on the circuit’s current.
You should remember that in the series RLC circuit, the following three formulas were used to find reactance, impedance, and power factor:
![]()
![]()
![]()
When working with a parallel circuit, you must use the following formulas instead:
![]()
![]()
![]()
The impedance of a parallel circuit is found by the formula:
![]()
Note: If no value for E is given in a circuit, any value of E can be assumed to find the values of IL, IC, IX, IR, and IZ.
Use the same voltage value to find the impedance.
Example Problem: Find the value of Z in the circuit shown above.
Given:
E = 300V
R = 100Ω
XL = 50Ω
XC =150Ω
The first step in solving for Z is to calculate the individual branch currents.
Solution:
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Using the values for IR, IL, and IC, solve for IX and IZ.
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Using IZ, Solve for Z
![]()
![]()
![]()
If the value for E was not given and you were asked to solve for Z, any value of E could be assumed. If in the example problem above, you assume a value of 50 volts for E, the solution would be:
Given:
R = 100
XL = 50
XC = 150
E = 50 V (assumed)
The first step in solving for Z is to calculate the individual branch currents.
Solution:
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Using the values for IR, IL, and IC, solve for IX and IZ.
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Using IZ, Solve for Z
Example Problem: When the voltage is given, you can use the values of currents, IR, IX, and IZ to calculate for the true power, reactive power, apparent power, and power factor.
For the circuit shown below, the calculations would be as follows.
Given:
E = 300V
R = 100Ω
IR = 3A
IX = 4A (inductive)
IZ = 5A
Z = 60Ω
Solution:
True Power = (IR)2R
True Power = (3A)2 x 100Ω
True Power = 900 Ω
To find X:
![]()
![]()
![]()
Reactive power = X = (IX)2X
Reactive power = (4A)2 x 75Ω
Reactive power = 1200 var
Apparent power = (Iz)2Z
Apparent power = (5A)2 x 60Ω
Apparent power = 1500 VA
Either of the following methods finds the power factor in a parallel circuit:
Given:
True Power = 900 Ω
Apparent power = 1500 VA
Solution:
![]()
![]()
![]()